Digitalization of energy for transformer stations.
Simplicity and usability in a solution for uninterrupted installation and comprehensive energy data reading.
Energy efficiency leads to positive results
The transformers and current sensors from Smilics Technologies have been designed with a split core to allow for easy opening and installation without interrupting the power supply.
The current transformers from the Sensors family feature a high level of precision, safety, and versatility, with a wide range of sizes and dimensions for the inner window.
SC3 current transformer is composed by three holes for three wire independent installation, with a maximum diameter of 14 mm.
This device has been designed to perfectly match the size of a 125 A MCCB.
TP Clip device is a small clamp type current transformer for cables up to 20 mm in diameter.
This line of devices covers a primary current range of 40 – 250 A, with secondary outputs of 1 or 5 A.
STP series split-core transformers range in current rating from 100 to 1000 A, according to the model, and provides 0,25, 1 or 5 A secondary outputs.
The Loop split-core transformers have a circular shape and an inner window for the passage of cables with a diameter of 80 or 105 mm. Depending on their use, these transformers are manufactured with either an output cable for outdoor installation or a terminal block connector, recommended for indoor use.
TP-420 series transformers include a converter to obtain a secondary current in the range 4-20 mA.
This devices have a use recommendation where a process signal proportional to the current needs to be carried to an automaton or PLC and commonly used in industrial automation and process control.
The TP series of transformers consists of various models that allow for their installation on a wide range of busbars or power cables without interrupting the power supply.
TP WG family products are homopolar current transformers, which measure the current of the three phases and verify that the circuit is well balanced.
They are used combining ground leaks or homopolar relays.
The set of Push transformers has been carefully developed to improve the installation of CTs: it features a button to open the core, allowing the device to be separated into two parts and easily installed in complex wiring systems.
AM Flex range of active coils are powered at 5V and the standard full scale output voltage is 1.28V. This product supports 100A/1kA/10kA scaling using a train of pulses.
R Flex active devices are powered at 9 – 12 V and allow 100/1kA/10kA or 200A/2kA/20kA scale switching through logical selection.
Typical full scale output voltage is 2V.
AMS Flex models have been designed with an easy-to-install grip and an open connector. The device is powered at 5 V, provides 100A/200A scale change and 1.28 V output.
S Flex passive models have been designed with an easy-to-install grip and an open connector. The output ratio of these devices is 37 mV/1kA@50Hz.
Flexible passive sensors in the C Flex series allow alternating current measurements with a ratio of 89mV/kA@50Hz.
Magnet Flex passive models have been designed with a magnetic sealable connector to hold both ends and make installation easier.
The output ratio of it is 100 mV/1kA@50Hz.
Convert the typical mV output of Rogowski coils into any standard measuring or protective device of …/1A. Thanks to its compact design, it only requires a DIN module. This device kit includes both the adapter and a flexible sensor.
Your network, under control
2Grid is a comprehensive solution for the monitoring and control of low-voltage transformer substations for electric power distribution companies.
Each device has been designed to provide electrical and environmental parameters from inside a transformer substation